SWIFT 10 MC Sensors
30
Transducer Interface
Hardware Overview
The TI transforms four inputs (amplified bridge signals) into two forces and one
moment by the following process:
Applying a zero offset and scaling the signals
Using a geometric matrix to transform the signals into two forces and one
moment in the transducer reference frame
Using a cross-coupling matrix calculation to scale and sum the individual
signals into each output
In spinning applications, using a rotational transformation to put the forces
and moments into a stationary reference frame
The TI conditions the transducer signals, producing four analog output signals
proportional to the following values:
Longitudinal force (Fx)
Vertical force (Fz)
Driving/Braking moment (My)
Angle output (θ)
Analog signals The force and moment signals are output from the TI in the form of ±10 V
1
full
scale analog signals. These signals can be used by most data acquisition systems.
The angle output is an analog voltage that is proportional to angular position. At
0° the output is 0 V. At 360°, the output is 5 V.
Fx1
Fx2
Fz1
Fz2
Fx
Fz
My
Geometric
Matrix
Zero and
Scaling
θ
Cross
Coupling
Matrix
Rotational
Transformation
θ
Inputs Output
s
Transducer Interface Functions
S10MC-06
1. Standard from MTS. Other full-scale output voltages can be evaluated and may be
provided at special request.