Specifications–Model 494.20 Chassis
All equipment related to the controller should be connected to the same fused
power circuit.
Note Electrical connections must be made by qualified personnel and conform
to local codes and regulations. Local electrical codes supersede any
information found here.
Model 494.20 Chassis 24 V DC Output
The Model 494.20 Chassis includes a 24 V DC Output that you can use to power
external devices. The output is fused with a 15 A, 250 V, fast fuse.
Cable specification To maintain EMC compliance, 24 V DC Output cables must comply with the
following specifications:
Connector–4-contact, Amphenol Series 97 connector.
Backshell–EMI metal.
Model 494.20 Chassis Specifications
P
ARAMETER SPECIFICATION
Input Voltage 100–240 V AC (single phase)
power factor corrected universal input
Input Frequency 50–60 Hz
Input Current 16 A at 100 V AC
8 A at 240 V AC
Facility Power Requirements Provide a dedicated circuit for the
chassis, computer, and monitor.
Input Surge <100 A
Insulation Over Voltage Category I
Pollution Degree 2
Weight Approximately 60 kg (132 lb)
Dimensions Width: 60 cm (24 in)
Height: 98 cm (38 in)
Depth: 90 cm (35 in)